Quick answer
A PowerFlex 525 that faults stops the motor and flashes the fault number (F followed by a number, for example F004) with the red fault light. Read the code, find it in the table below, fix the cause, then clear it with the Stop key, a power cycle or A551 [Fault Clear]. Type 1 faults may reset by themselves if auto restart is set up; Type 2 faults need the cause fixed before they clear.
Jump to a code:
Safety first: lock out and tag out the drive and the machine before you open the drive or touch the wiring, and follow Rockwell Automation's procedure in the manual. The drive's DC bus capacitors stay charged after power is removed: the manual says to wait at least 3 minutes, then measure DC+ to DC–: a qualified person verifies zero voltage with a properly rated meter, checking the meter on a known source before and after – a dark display doesn't mean it's safe. Never bypass a safety circuit or switch off a fault to keep a machine running. Only qualified personnel should work on drives, and any measurement on energized equipment follows your site's live-work and arc-flash rules.
Reading and clearing a PowerFlex 525 fault
- Note the code. Press Esc to acknowledge the fault so you can use the keypad. b007 [Fault 1 Code] holds the latest fault, b008 and b009 the two before it, and F604 to F610 go back to the tenth.
- Look it up in the table below or in the manual, and fix the cause first – a fault whose cause is still there comes straight back.
- Clear it: press Stop (when P045 [Stop Mode] is set from 0 to 3), cycle power, set A551 [Fault Clear] to 1 “Reset Fault”, or use a digital input programmed as Clear Fault.
- Watch the restart. If the same code returns, go back through the checks before resetting again.
The PowerFlex 523 uses the same user manual and fault list; codes marked “PowerFlex 525 only” don't apply to it.
Common PowerFlex 525 fault codes
This list covers the codes technicians run into most often, not every code. The manual has the complete list and the full corrective actions.
| Code | What it means | Likely causes | First checks |
|---|---|---|---|
| F002Auxiliary InputType 1 | The external trip input opened, or the network commanded a fault. |
|
|
| F003Power LossType 2 | The drive saw single-phase input while carrying too much load. |
|
|
| F004UnderVoltageType 1 | The DC bus voltage dropped below the drive's minimum. |
|
|
| F005OverVoltageType 1 | The DC bus voltage rose above the drive's maximum. |
|
|
| F006Motor StalledType 1 | The drive could not accelerate or decelerate the motor; it was held at its current limit too long. |
|
|
| F007Motor OverloadType 1 | The drive's electronic motor overload protection tripped. |
|
|
| F008Heatsink OvrTmpType 1 | The heatsink / power module got too hot. |
|
|
| F012HW OverCurrentType 2 | Output current went past the drive's hardware current limit. |
|
|
| F013Ground FaultType 1 | The drive found a current path to ground on one or more output terminals. |
|
|
| F015Load LossType 2PowerFlex 525 only | Torque current stayed below the set load-loss level for longer than the set time. |
|
|
| F021Output Ph LossType 1 | An output phase is missing (only when output phase loss detection is turned on). |
|
|
| F029Analog In LossType 1 | An analog input set to fault on signal loss lost its signal. |
|
|
| F033Auto Rstrt TriesType 2 | The drive used up its programmed auto-restart attempts without clearing the original fault. |
|
|
| F038 / F039 / F040Phase U to GndType 2 | A phase-to-ground fault was found between the drive and the motor on that phase (U, V or W). |
|
|
| F041 / F042 / F043Phase UV ShortType 2 | Excessive current was found between two output terminals (U-V, U-W or V-W). |
|
|
| F048Params DefaultedType 1 | The drive was told to write its factory default settings. |
|
|
| F059Safety OpenType 1PowerFlex 525 only | Both Safe Torque Off inputs (Safety 1 and Safety 2) are off. |
|
|
| F063SW OverCurrentType 1 | Current stayed above the programmed shear-pin level for longer than the shear-pin time. |
|
|
| F064Drive OverloadType 2 | The drive's own overload rating was exceeded. |
|
|
| F070Power UnitType 2 | The drive detected a failure in its power section. |
|
|
| F071DSI Net LossType 2 | Control over the Modbus or DSI link was lost. |
|
|
| F073EN Net LossType 2PowerFlex 525 only | Control through the built-in EtherNet/IP port was lost. |
|
|
| F081DSI Comm LossType 2 | Communication between the drive and its Modbus or DSI master was interrupted. |
|
|
| F100Parameter ChksumType 2 | The drive's stored parameter memory is corrupt. |
|
|
| F111Safety HardwareType 2PowerFlex 525 only | A fault in the Safe Torque Off input hardware: only one of the two safety inputs is on. |
|
|
| F114uC FailureType 2 | The drive's microprocessor failed. |
|
|
| F122I/O Board FailType 2 | A failure was detected in the drive's control and I/O section. |
|
|
The fault name is the short text the drive shows. Rarer codes in the same manual chapter that this page doesn't cover: F009, F072, F080, F082, F083, F091, F094, F101, F105, F106, F107, F109, F110, F125, F126, F127 – see the manual for those.
Source: Rockwell Automation, PowerFlex 520-series Adjustable Frequency AC Drive User Manual, publication 520-UM001O-EN-E (September 2025) – Chapter 4, Troubleshooting: Fault Types, Descriptions, and Actions, read on October 17, 2026.
Meanings, causes and checks are summarized in our own words. The manual is the reference: it has every code, the full corrective actions and the safety instructions. A newer revision of the manual may add codes, so check the current revision for your drive.
Allen-Bradley AC drives in stock
We have no PowerFlex 525 in stock right now. These are other Allen-Bradley AC drives on our shelves; for a PowerFlex 525, send us the catalog number and we'll check our sourcing network.
- SD3000Rockwell Automation SD3000 Plus Drive Control SD3K-2004 SER A REV B01 120VAC 2A
- 20AD3P4A0AYNNNNNAllen-Bradley 20AD3P4A0AYNNNNN PowerFlex 70 AC Drive 2HP 480V 3 Phase VFD Ser A
- 1336F-BRF20-AE-ITAllen-Bradley 1336F-BRF20-AE-IT 1336 Plus II Sensorless Vector AC Drive 20HP VFD
- 1336F-BRF20-AEAllen-Bradley 1336F-BRF20-AE 1336 Plus II Sensorless Vector AC Drive 20HP VFD
- 20-COMM-PAllen-Bradley 20-COMM-P Series A PROFIBUS DP Adapter PowerFlex Drive Module
- 20AD3P4A3AYYNDNNAllen-Bradley 20AD3P4A3AYYNDNN PowerFlex 70 VFD 2HP 480V 3.4A with HIM Keypad
- 20D-DL2-ENET0Allen-Bradley 20D-DL2-ENET0 Spare Parts Kit Ethernet Comm Module PowerFlex 700S
- 22A-D6P0N104Allen Bradley 22A-D6P0N104 SER A 3 Phase, 380-480V,48-63Hz
Fault won't clear?
When the checks point to the drive itself – the manual's “replace the drive” or “replace the control module” – send us the fault code and the catalog number from the nameplate. We check our shelves and our sourcing network and reply with a written quote. Purchase orders are welcome; payment is due before we ship.
Frequently asked questions
How do I clear a fault on a PowerFlex 525?
Press Esc to acknowledge it, fix what caused it, then clear it: press Stop (when P045 [Stop Mode] is 0 to 3), cycle power, set A551 [Fault Clear] to 1, or use a digital input set to Clear Fault. A fault comes straight back if its cause is still there.
What is the difference between a Type 1 and a Type 2 fault?
A Type 1 fault can be reset by the drive's auto restart (A541 [Auto Rstrt Tries] and A542 [Auto Rstrt Delay]) once the condition is gone. A Type 2 fault is never auto-reset: it points to wiring, programming or hardware, and the cause has to be fixed before it can be cleared.
Where can I see which faults a PowerFlex 525 had?
b007 [Fault 1 Code] holds the most recent fault, b008 and b009 the two before it, and F604 to F610 go back to the tenth. A fault that repeats is recorded once.
Do these fault codes apply to the PowerFlex 523?
Mostly yes: the PowerFlex 523 and 525 share one user manual and one fault list. Load Loss (F015), Safety Open (F059), EN Net Loss (F073), EN Comm Loss (F083), Encoder Loss (F091) and Safety Hardware (F111) are PowerFlex 525 only.
Can you supply a replacement PowerFlex 525 drive or control module?
Send the catalog number from the nameplate and the fault code through our quote form. We check our shelves and our sourcing network and reply with a written quote.