Quick answer
A SINAMICS drive shows a fault as F plus five digits (for example F30002) and an alarm as A plus five digits (for example A07910). A fault makes the drive react – OFF1 ramps the motor down, OFF2 switches the pulses off so it coasts, OFF3 is a quick stop – and stays until it is acknowledged. An alarm is a warning that clears itself once its cause is gone. Find the code below, fix the cause, then acknowledge the fault.
Jump to a code:
Safety first: lock out and tag out the drive and the machine before you open a drive or touch the wiring, and follow Siemens' safety instructions in the hardware manual for your power unit. The DC link capacitors stay charged after power is removed: Siemens' manuals for the PM240-2 Power Module and the S120 booksize power units say to wait 5 minutes (other power units give their time on the warning label); then a qualified person, with a properly rated meter checked on a known source before and after, confirms that there is no voltage between any of the power terminals and between them and ground – a dark display doesn't mean it's safe. Never bypass Safe Torque Off or any other safety circuit, and never switch off a fault to keep a machine running. Only qualified personnel should work on drives, and any measurement on energized equipment follows your site's live-work and arc-flash rules.
Reading and acknowledging a SINAMICS fault
- Note the code and its value. r0945 lists the fault codes – the current fault case and the last seven acknowledged ones – and r0949 holds each fault's value, which many codes use to say which phase or which bit tripped. r2122 lists the alarm codes.
- Look it up in the table below or in the List Manual, and fix the cause first – a fault whose cause is still there comes straight back.
- Acknowledge it the way the table's “Ack” says: IMMEDIATELY – set p3981 from 0 to 1, give a 0-to-1 edge on the input set in p2103, send control word bit STW1.7 from the PLC, or power-cycle; POWER ON – switch the drive off and on; PULSE INHIBIT – only once the pulses are off. Safe Torque Off has to be deselected before a Safety Integrated fault can be acknowledged.
- Watch the restart. If the same code returns, go back through the checks before acknowledging again.
One page for G120 and S120
The G120 and S120 List Manuals use the same SINAMICS numbering: every shared code in the table has the same number in both, and the same name apart from a few wording differences noted in the table (for example F08501 and A08526, which the S120 manual calls PN/COMM BOARD messages). The S120 adds its own ranges for the infeed (Line Modules, F06xxx) and for encoders on DRIVE-CLiQ (F31xxx); rows marked “S120 only” or “G120 only” are in one of the two manuals only. On an S120 the same power unit code (F30xxx) can come from a Motor Module or from the Line Module, so check which drive object reports it. A message's reaction and type can be changed with parameters, so a drive that was set up differently may react differently from the defaults shown here.
Common SINAMICS G120 / S120 fault codes
This list covers the codes technicians run into most often, not every code – the List Manuals have hundreds more. The manuals have the complete list, the fault values and the full remedies.
| Code | What it means | Likely causes | First checks |
|---|---|---|---|
| F07801Drive: Motor overcurrentAck: IMMEDIATELY OFF2 | Motor current went above the motor current limit the drive is allowed to deliver. |
|
|
| F07802Drive: Infeed or power unit not readyAck: IMMEDIATELY OFF2 | After the switch-on command, the infeed or the power unit did not report ready in time. |
|
|
| F07807Drive: Short-circuit/ground fault detectedAck: IMMEDIATELY OFF2 | The drive found a phase-to-phase short or a ground fault at its motor terminals. |
|
|
| F07011 / A07910Drive: Motor overtemperatureAck: IMMEDIATELY OFF2 | The motor's temperature sensor or the drive's motor thermal model is over the limit; A07910 is the warning stage before it. |
|
|
| F07900Drive: Motor blockedAck: IMMEDIATELY OFF2 | The motor ran at its torque limit below a set speed for longer than the set time. |
|
|
| F07901Drive: Motor overspeedAck: IMMEDIATELY OFF2 | Motor speed went past the maximum speed plus the set margin, in either direction. |
|
|
| F07902Drive: Motor stalledAck: IMMEDIATELY OFF2 | The drive's motor model decided the motor stalled for longer than the set time (p2178). |
|
|
| F07860 / F07861 / F07862External fault 1Ack: IMMEDIATELY OFF2 | A signal wired to the external fault input dropped (a 1 to 0 change); F07861 and F07862 are inputs 2 and 3. |
|
|
| F07320Drive: Automatic restart interruptedAck: IMMEDIATELY OFF2 | Automatic restart used up its restart attempts without the original fault clearing. |
|
|
| F07806Drive: Regenerative power limit exceeded (F3E)Ack: IMMEDIATELY OFF2G120 only | A PM250 or PM260 Power Module fed back more than its rated regenerative power for over 10 s. |
|
|
| F07412Drive: Commutation angle incorrect (motor model)Ack: IMMEDIATELY ENCODERS120 only | The drive found that the encoder's rotor position does not match its motor model. |
|
|
| F30001Power unit: OvercurrentAck: IMMEDIATELY OFF2 | The power unit's own current monitoring tripped; the fault value r0949 shows which phase. |
|
|
| F30002Power unit: DC link voltage overvoltageAck: IMMEDIATELY OFF2 | The DC link voltage went above the power unit's limit. |
|
|
| F30003Power unit: DC link voltage undervoltageAck: IMMEDIATELY OFF2 | The DC link voltage dropped below the power unit's minimum. |
|
|
| F30004Power unit: Overtemperature heat sink AC inverterAck: IMMEDIATELY OFF2 | The power unit's heat sink got too hot; A05000 is the warning stage. |
|
|
| F30005Power unit: Overload I2tAck: IMMEDIATELY OFF2 | The power unit carried more than its rated current for too long (r0036 reached 100 %). |
|
|
| F30011Power unit: Line phase failure in main circuitAck: IMMEDIATELY OFF2 | DC link ripple got too high, which usually means a missing or unbalanced line phase. |
|
|
| F30015Power unit: Phase failure motor cableAck: IMMEDIATELY OFF2 | The drive found a missing phase on the motor cable. |
|
|
| F30021Power unit: Ground faultAck: IMMEDIATELY OFF2 | The power unit found current flowing to ground. |
|
|
| F30024Power unit: Overtemperature thermal modelAck: IMMEDIATELY OFF2 | The drive's thermal model of its power semiconductors went over the limit. |
|
|
| F30027Power unit: Precharging DC link time monitoringAck: IMMEDIATELY OFF2 | The DC link did not charge up within the expected time at switch-on. |
|
|
| F30036Power unit: Internal overtemperatureAck: IMMEDIATELY OFF2 | The temperature inside the drive went over the limit. |
|
|
| F30059Power unit: Internal fan faultyAck: IMMEDIATELY OFF2 | The power unit's internal fan has failed. |
|
|
| F01910Fieldbus interface setpoint timeoutAck: IMMEDIATELY OFF3 | The drive stopped receiving setpoints over the fieldbus (PROFIBUS, PROFINET or USS). |
|
|
| F08501PROFINET: Setpoint timeoutAck: IMMEDIATELY OFF3 | Setpoints over PROFINET stopped arriving; the S120 List Manual names it “PN/COMM BOARD: Setpoint timeout” (a COMM BOARD, CBE20). |
|
|
| A08526PROFINET: No cyclic connectionAlarm | No cyclic connection to a PROFINET controller (an alarm; it clears itself). The S120 List Manual names it “PN/COMM BOARD: No cyclic connection”. |
|
|
| F07220Drive: Master control by PLC missingAck: IMMEDIATELY OFF1 | The “master control by PLC” signal dropped while the drive was running. |
|
|
| F03505Analog input wire breakageAck: IMMEDIATELY OFF1 | An analog input with wire-break monitoring fell below its threshold (p0761). |
|
|
| F01600SI P1 (CU): STOP A initiatedAck: IMMEDIATELY OFF2 | Safety Integrated found a problem and switched the motor torque off (STOP A, Safe Torque Off). |
|
|
| F06100Infeed: Shutdown due to line supply undervoltage conditionAck: IMMEDIATELY OFF2S120 only | The Line Module measured a supply voltage below its trip threshold (p0283 × p0210). |
|
|
| F06200Infeed: One or several line phases failedAck: IMMEDIATELY OFF2S120 only | The Line Module lost one or more line phases, or could not lock on to the supply at switch-on. |
|
|
| F31110Encoder 1: Serial communications errorAck: PULSE INHIBIT ENCODERS120 only | The serial link between encoder 1 and its evaluation module failed; r0949 shows the error bits. |
|
|
| F31885Encoder 1 DRIVE-CLiQ (CU): Cyclic data transfer errorAck: IMMEDIATELY ENCODERS120 only | DRIVE-CLiQ data from encoder 1's Sensor Module to the Control Unit got out of step. |
|
|
The name is the message's own short text from the List Manual; “Ack” and the reaction are the manual's defaults. Other codes in the same manuals that this page doesn't cover: F01000, F01001, F01030, F01611, F01650, A01900, A01920, A05000, F06000, F06310, A07012, F07016, A07400, F07403, F07404, A07805, F07950, F30012, F30017, F30022, F30025, F30035, F30037, F30071, F30074, F31100, F31117 – see the List Manual for those and for every code not listed here.
Sources: Siemens, SINAMICS G120 Control Units CU240B-2/CU240E-2 List Manual, edition 02/2023, A5E33839529 (firmware 4.7 SP14) – chapter 4, Faults and alarms; Siemens, SINAMICS S120/S150 List Manual, edition 06/2020, 6SL3097-5AP00-0BP2 (firmware 5.2 SP3) – chapter 4, Faults and alarms. Safety (the DC link discharge time): SINAMICS G120 Power Module PM240-2 Hardware Installation Manual, 08/2017, A5E33294624B AG; SINAMICS S120 Power Units in Booksize C/D-Type Format Manual, 09/2017, 6SL3097-4AC20-0BP2. Read on October 17, 2026.
Meanings, causes and checks are summarized in our own words. The manuals are the reference: they have every code, the full remedies and the safety instructions. Codes, texts and defaults depend on the firmware version, so check the List Manual edition for your drive's firmware.
SINAMICS G120 / S120 parts in stock
SINAMICS G120 and S120 catalog numbers on our shelves right now. Every item is photographed, so check the rating plate – catalog number and version – against the part you're replacing.
- 6SL3252-0BB01-0AA0Siemens 6SL3252-0BB01-0AA0 Sinamics Safe Brake Module B01 18-30VDC Relay Unit
- 6SL3120-1TE23-0AA3Siemens 6SL3120-1TE23-0AA3 Sinamics Single Motor Module DC 600V 3AC 400V 30A
- 6SL3055-0AA00-5BA3Siemens 6SL3055-0AA00-5BA3 SMC20 Sinamics Sensor Module Cabinet-Mounted Drive
- 6SL3120-2TE15-0AA4Siemens 6SL3120-2TE15-0AA4 Sinamics Double Motor Module DC 600V 3AC 400V 5A/5A
- 6SL3130-7TE23-6AA3Siemens 6SL3130-7TE23-6AA3 Sinamics Active Line Module 36kW DC 600V 60A 380-480V
- 6SL3352-6BE00-0AA1Siemens 6SL3352-6BE00-0AA1 C98043-A7600-L5 Power Interface Board Drive Control
Fault won't clear?
When the checks point to the hardware itself – the List Manual's “replace the power unit”, “replace the component” or “replace the Control Unit” – send us the fault code and the catalog number from the rating plate. We check our shelves and our sourcing network and reply with a written quote. Purchase orders are welcome; payment is due before we ship.
Frequently asked questions
How do I acknowledge a fault on a SINAMICS G120 or S120?
Fix the cause first, then acknowledge: set p3981 from 0 to 1, give a 0-to-1 edge on the input set in p2103 (on a CU240B-2 / CU240E-2 without fieldbus that is digital input DI 2 in the factory setting), send control word bit STW1.7 from the PLC, or switch the drive off and on. A code whose acknowledgement is POWER ON needs the power cycle, and Safe Torque Off has to be deselected before a Safety Integrated fault can be acknowledged.
What is the difference between an F code and an A code?
An F code is a fault: the drive reacts (OFF1 ramps down, OFF2 lets the motor coast, OFF3 is a quick stop), records it in the fault buffer and waits to be acknowledged. An A code is an alarm: a warning that clears itself once its cause is gone. Letters in brackets after a code in the List Manual mean its type can be changed with p2118 / p2119.
Are SINAMICS G120 and S120 fault codes the same?
Largely yes. Both List Manuals use the same SINAMICS numbering: the codes shared on this page have the same number in both, and the same name apart from a few wording differences noted in the table. The S120 adds infeed (Line Module) codes F06xxx and DRIVE-CLiQ encoder codes F31xxx; rows marked “S120 only” or “G120 only” appear in one of the two manuals only.
Where can I see which faults a SINAMICS drive had?
r0945 lists the fault codes: the current fault case and the last seven acknowledged ones, up to eight faults each, with r0949 holding each fault's value. r2122 lists the alarm codes, and r2131 / r2132 show the current fault and alarm code.
Can you supply a replacement SINAMICS control unit, Power Module or Motor Module?
Send the catalog number from the rating plate (it starts 6SL3 on G120 and S120 parts) and the fault code through our quote form. We check our shelves and our sourcing network and reply with a written quote.