Quick answer
An FR-E800 that trips shuts off its output, sends the Fault (ALM) signal and shows E. and a short code on the operation panel – for example E.OC1. Warnings such as OLC, OLV, UV or TH and the FN fan alarm don't trip the inverter by themselves, but the manual says a warning leads to a fault if nothing is done. Find the code below, fix the cause, make sure the start signal is off, then reset with the STOP/RESET key, the RES input or a power cycle.
Jump to a code:
Safety first: lock out and tag out the inverter and the machine before you open the inverter or touch the wiring, and follow Mitsubishi Electric's precautions in the manuals. The smoothing capacitors stay charged after power is removed: the Maintenance manual says to wait 10 minutes or longer; then a qualified person, with a properly rated meter checked on a known source before and after, confirms that the voltage between main circuit terminals P/+ and N/– is 30 V DC or less – a dark display doesn't mean it's safe. If the panel shows EV (the inverter runs on an external 24 V supply), switch that supply off too. Never bypass the safety stop inputs (S1, S2) or any other safety circuit, and never switch off a fault or raise the retry count to keep a machine running – the retry function restarts the motor by itself. Only qualified personnel should work on inverters, and any measurement on energized equipment follows your site's live-work and arc-flash rules.
Reading and resetting an FR-E800 fault
- Note the code. The operation panel's fault history keeps the last ten faults, each with the output frequency, current and voltage and the energization time when it happened. Er.CL clears it.
- Look it up in the table below or in the manual, and fix the cause first – a fault whose cause is still there comes straight back.
- Reset it: turn the start signal off first – the manual warns that a reset with it on restarts the motor suddenly – then press STOP/RESET, turn on the RES signal for 0.1 s or more, or switch the power off and on. The IP67 model's panel has no STOP/RESET key.
- Watch the restart. If the same code returns, go back through the checks before resetting again.
One Maintenance manual covers the FR-E800 standard, Ethernet, safety communication (SCE), IP67 and CC-Link (NC) models. Some codes apply only to certain models, motors or control methods (PM motors, vector control), and codes marked “Off in the initial setting” only appear once their function has been turned on.
Common FR-E800 fault codes
This list covers the codes technicians run into most often, not every code. The manual has the complete list and the full corrective actions.
| Code | What it means | Likely causes | First checks |
|---|---|---|---|
| E.OC1Overcurrent trip during accelerationFault | Output current went over the trip level (about 230 % of rated current at the ND rating) while accelerating. |
|
|
| E.OC2Overcurrent trip during constant speedFault | Output current went over the trip level while running at a steady speed. |
|
|
| E.OC3Overcurrent trip during deceleration or stopFault | Output current went over the trip level while slowing down or stopped. |
|
|
| E.SCFOutput short-circuitFaultOff in the initial setting | An output short circuit was found (only with Pr.521 = 1; otherwise it shows as E.OC1 to E.OC3). |
|
|
| E.OV1Regenerative overvoltage trip during accelerationFault | Regenerated energy pushed the internal DC voltage too high while accelerating; a supply surge can do it too. |
|
|
| E.OV2Regenerative overvoltage trip during constant speedFault | Regenerated energy pushed the internal DC voltage too high at a steady speed. |
|
|
| E.OV3Regenerative overvoltage trip during deceleration or stopFault | Regenerated energy pushed the internal DC voltage too high while slowing down or stopped. |
|
|
| E.THTInverter overload trip (electronic thermal relay function)Fault | The output transistors' thermal protection tripped; the manual gives the overload capacity as 150 % for 60 s. |
|
|
| E.THMMotor overload trip (electronic thermal relay function)Fault | The motor's electronic thermal protection tripped; the TH warning comes first, at 85 %. |
|
|
| E.FINHeat sink overheatFault | The heat sink's temperature sensor tripped. |
|
|
| E.UVTUndervoltageFault | With a PM motor, supply dips made the motor coast and restart over and over. |
|
|
| E.ILFInput phase lossFault | One of the three input phases was lost (only with Pr.872 = 1). |
|
|
| E.OLTStall prevention stopFault | Stall prevention or the torque limit held the output at low speed for 3 seconds because of the load. |
|
|
| E.GFOutput side earth (ground) fault overcurrentFault | A ground fault on the output (load) side made the inverter shut off. |
|
|
| E.LFOutput phase lossFault | One of the output phases (U, V, W) was lost. |
|
|
| E.OHTExternal thermal relay operationFaultOff in the initial setting | A thermal relay or motor thermostat wired to the OH input opened. |
|
|
| E.PTCPTC thermistor operationFaultOff in the initial setting | The motor's PTC thermistor on terminal 2 read above the Pr.561 level for the Pr.1016 time. |
|
|
| E.BEBrake transistor alarm detectionFault | A fault in the brake circuit, such as a damaged brake transistor. |
|
|
| E.SAFSafety circuit faultFault | A safety circuit fault, or the S1–PC or S2–PC connection opened while the safety stop is in use. |
|
|
| E.PEParameter storage device fault (control circuit board)Fault | A fault in the stored parameters (the EEPROM) on the control board. |
|
|
| E.PE6Internal storage device faultFault | Writing to the internal storage failed, for example because power went off during a parameter operation. |
|
|
| E.PUEPU disconnectionFault | Communication with the PU, or RS-485 on the PU connector, was lost. |
|
|
| E.RETRetry count excessFaultOff in the initial setting | The retry function could not restart the inverter within the number of retries set in Pr.67. |
|
|
| E.CPU / E.5 / E.6 / E.7CPU faultFault | A communication fault of the built-in CPU. |
|
|
| E.IOHInrush current limit circuit faultFault | The inrush current limit resistor overheated. |
|
|
| E.AIEAnalog input faultFault | Terminal 2 or 4, set for current input, got 30 mA or more or 7.5 V or more. |
|
|
| E.EHREthernet communication faultFault | Ethernet communication was lost for the Pr.1432 time, or the network master stopped or timed out. |
|
|
| E.OP1Communication option faultFault | A communication line error in the plug-in communication option. |
|
|
| OLCStall prevention (overcurrent)Warning | Output current is over the stall prevention level, so the inverter holds or lowers the frequency. |
|
|
| OLVStall prevention (overvoltage)Warning | Regenerated energy is too much, so the inverter pauses the deceleration to avoid an overvoltage trip. |
|
|
| UVUndervoltageWarning | The supply fell to the undervoltage level for its voltage class; the output stays off until it recovers. |
|
|
| THElectronic thermal relay function pre-alarmWarning | The electronic thermal value reached 85 % of the Pr.9 setting; the inverter trips if it reaches the limit. |
|
|
| SASafety stopWarning | The safety stop function is active and the output is shut off. |
|
|
| CorCorrosion warningWarning | The control board's corrosion level reached 3 (coated FR-E800 models with -60 at the end only). |
|
|
| FNFan alarmAlarm | The cooling fan stopped, runs too slowly, or doesn't run the way Pr.244 sets it. |
|
|
The name is the manual's own name for the code; the code is what the operation panel shows. A warning or an alarm doesn't trip the inverter or send the Fault signal; SA and UV hold the output off while their cause lasts. Other error messages, warnings and faults in the same list that this page doesn't cover: HOLD, LOCD, Er1–Er4, Err., RB, PS, MT, SL, CF, LDF, EHR, DIP, IP, SE, LP, HP1–HP3, ED, E.SOT, E.LUP, E.LDN, E.OPT, E.16–E.20, E.PE2, E.USB, E.OS, E.OSD, E.ECT, E.OD, E.MB1–E.MB7, E.EP, E.OA, E.IAH, E.PID, E.CDO, E.CMB, E.1, E.10, E.11, E.13 – see the manual for those.
Sources: Mitsubishi Electric, FR-E800 Instruction Manual (Maintenance), IB(NA)-0600874ENG-P (December 2025) – chapter 2, Protective Functions (List of fault displays; Causes and corrective actions); Mitsubishi Electric, FR-E800 Instruction Manual (Function), IB(NA)-0600868ENG-U (May 2026) – monitor item selection (Pr.52) and the retry function (Pr.65, Pr.67, Pr.68), read on October 17, 2026.
Meanings, causes and checks are summarized in our own words. The manuals are the reference: they have every code, the full corrective actions and the safety instructions. A newer revision of a manual may add codes, so check the current revision for your drive.
FR-E800 inverters in stock
Mitsubishi FR-E800 (FR-E820, FR-E840) part numbers on our shelves right now. Every item is photographed, so check the nameplate – catalog number and series – against the drive you're replacing.
- FR-E840-0026-5-60Mitsubishi FR-E840-0026-5-60 FREQROL E800 VFD Inverter Drive 3PH 380-480V 4.4A
- FR-E840-0095-5-60Mitsubishi FR-E840-0095-5-60 Inverter 3PH AC380-480V480Y/277V 50/60Hz
Fault won't clear?
When the checks point to the drive itself – the manual's “replace the inverter” or “contact your sales representative” – send us the fault code and the catalog number from the nameplate. We check our shelves and our sourcing network and reply with a written quote. Purchase orders are welcome; payment is due before we ship.
Frequently asked questions
How do I reset a fault on a Mitsubishi FR-E800?
Fix the cause first and turn the start signal off – a reset with the start signal on restarts the motor suddenly. Then press STOP/RESET on the operation panel, turn on the RES signal for 0.1 s or more, or switch the power off and on. A reset also clears the electronic thermal count and the retry count.
What does E.OV3 mean on a Mitsubishi FR-E800?
E.OV3 is the regenerative overvoltage trip during deceleration or stop: energy coming back from the motor pushed the inverter's internal DC voltage too high. Lengthen the deceleration time, use the regeneration avoidance function, or add a brake resistor or brake unit for loads that keep regenerating.
What is the difference between OLC, OLV and E.OLT?
OLC and OLV are warnings: stall prevention is holding the frequency back because of high current (OLC) or high regenerated voltage (OLV), and the inverter keeps running. E.OLT is the fault that follows when stall prevention or the torque limit holds the motor at low speed for 3 seconds.
Are FR-E700 and FR-E800 fault codes the same?
Many codes carry the same names (E.OC1 to E.OC3, E.OV1 to E.OV3, E.THT, E.THM, E.FIN), but the FR-E800 adds codes such as E.UVT, E.PTC, E.EHR, E.PE6 and E.CMB and names its stall prevention warnings OLC and OLV. Use the manual for your series; we have a separate FR-E700 page.
Can you supply a replacement FR-E800 inverter?
Send the model from the rating plate (for example FR-E840-...) and the fault code through our quote form. We check our shelves and our sourcing network and reply with a written quote.