Quick answer
An FR-E700 that trips shuts off its output, sends its fault signal and shows the fault on the operation panel as E. and a short code – for example E.OC1. Warnings such as OL and TH and the FN fan alarm don't stop the output; UV shuts the output off until the supply recovers. The manual says a warning leads to a fault if nothing is done. Find the code below, fix the cause, make sure the start signal is off, then reset with the STOP/RESET key, the RES input or a power cycle.
Jump to a code:
Safety first: lock out and tag out the inverter and the machine before you open the inverter or touch the wiring, and follow Mitsubishi Electric's precautions in the manual. The smoothing capacitors stay charged after power is removed: the manual says to wait at least 10 minutes, check that the operation panel display is off; then a qualified person, with a properly rated meter checked on a known source before and after, confirms that the voltage between main circuit terminals P/+ and N/– is 30 V DC or less – a dark display alone doesn't mean it's safe. If the panel shows EV (the inverter is running on an external 24 V supply), switch that supply off too. Never bypass the safety stop inputs (S1, S2) or any other safety circuit, and never switch off a fault or raise the retry count to keep a machine running – the retry function restarts the motor by itself. Only qualified personnel should work on inverters, and any measurement on energized equipment follows your site's live-work and arc-flash rules.
Reading and resetting an FR-E700 fault
- Note the code. The operation panel's faults history mode shows the past eight faults, each with the output frequency, current, voltage and energization time when it happened. Er.CL clears the history.
- Look it up in the table below or in the manual, and fix the cause first – a fault whose cause is still there comes straight back.
- Reset it: turn the start signal (STF / STR) off first – the manual warns that a reset with it on restarts the motor at once – then press STOP/RESET, turn on the RES signal for more than 0.1 s, or switch the power off and back on once the panel has gone dark.
- Watch the restart. If the same code returns, go back through the checks before resetting again.
The table follows the Instruction Manual (Basic) for the FR-E700 safety stop (SC) models; the Instruction Manual (Applied) for the CC-Link (NC) models describes the same E.OC, E.OV, E.TH and E.FIN codes. Other FR-E700 versions have their own manuals and some codes depend on the model and its options, so check the manual for your inverter's model. Codes marked “Off in the initial setting” only appear once their function has been turned on.
Common FR-E700 fault codes
This list covers the codes technicians run into most often, not every code. The manual has the complete list and the full corrective actions.
| Code | What it means | Likely causes | First checks |
|---|---|---|---|
| E.OC1Overcurrent trip during accelerationFault | Output current went over the trip level while the motor was accelerating. |
|
|
| E.OC2Overcurrent trip during constant speedFault | Output current went over the trip level while running at a steady speed. |
|
|
| E.OC3Overcurrent trip during deceleration or stopFault | Output current went over the trip level while slowing down or stopped. |
|
|
| E.OV1Regenerative overvoltage trip during accelerationFault | The DC bus voltage went too high while the motor was accelerating. |
|
|
| E.OV2Regenerative overvoltage trip during constant speedFault | The DC bus voltage went too high while running at a steady speed. |
|
|
| E.OV3Regenerative overvoltage trip during deceleration or stopFault | The DC bus voltage went too high while slowing down or stopped. |
|
|
| E.THTInverter overload trip (electronic thermal O/L relay function)Fault | The inverter's electronic thermal protection for its own output transistors tripped. |
|
|
| E.THMMotor overload trip (electronic thermal O/L relay function)Fault | The inverter's electronic thermal protection for the motor tripped. |
|
|
| E.FINHeatsink overheatFault | The heatsink got too hot. |
|
|
| E.ILFInput phase lossFaultActive only when Pr.872 = 1; check your setting | One of the three input phases is missing, or the phases are badly unbalanced. |
|
|
| E.OLTStall prevention stopFault | Stall prevention brought the output down to 1 Hz because the load was too heavy. |
|
|
| E.GFOutput side earth (ground) fault overcurrent at startFaultOff in the initial setting | A ground fault on the output side was found when the inverter started. |
|
|
| E.LFOutput phase lossFault | One of the output phases (U, V, W) was lost while the inverter was running. |
|
|
| E.OHTExternal thermal relay operationFaultOff in the initial setting | A thermal relay or motor thermostat wired to the OH input opened. |
|
|
| E.BEBrake transistor alarm detectionFault | The inverter found a fault in its brake circuit, such as a failed brake transistor. |
|
|
| E.SAFSafety circuit faultFault | A safety circuit fault, or the S1–PC or S2–PC safety stop connection opened. |
|
|
| E.PEParameter storage device faultFault | The part of the control board that stores the parameters stopped working normally. |
|
|
| E.PUEPU disconnectionFault | Communication with the parameter unit, or RS-485 on the PU connector, was lost. |
|
|
| E.RETRetry count excessFaultOff in the initial setting | The retry function could not restart the inverter within the set number of tries. |
|
|
| E.CPU / E.5 / E.6 / E.7CPU faultFault | An error in the CPU or the circuits around it. |
|
|
| E.AIEAnalog input faultFault | Terminal 4 got a signal while Pr.267 and the voltage / current input switch were set differently. |
|
|
| E.IOHInrush current limit circuit faultFault | The resistor in the inrush current limit circuit overheated. |
|
|
| E.USBUSB communication faultFault | USB communication was broken for longer than the time set in Pr.548. |
|
|
| E.OP1Communication option faultFault | A communication error on the line of a communication option. |
|
|
| OLStall prevention (overcurrent)Warning | Overcurrent stall prevention is working: the inverter holds back the frequency to limit the current. |
|
|
| UVUndervoltageWarning | The supply fell below about 115 V AC (230 V AC on 400 V models); the output is off until it recovers. |
|
|
| THElectronic thermal relay function prealarmWarning | The electronic thermal value reached 85 % of the Pr.9 setting; a trip follows if it keeps rising. |
|
|
| PSPU stopWarning | STOP/RESET on the operation panel was pressed while the inverter was in External operation. |
|
|
| SASafety stopWarning | The safety stop function is active and the output is shut off. |
|
|
| FNFan alarmAlarm | The cooling fan stopped or slowed down while it should be running. |
|
|
The name is the manual's own name for the code; the code is what the operation panel shows. A warning or an alarm doesn't trip the inverter or send the fault signal. OL and TH don't stop the output; UV shuts the output off until the supply recovers, and during SA the safety stop holds it off. Other error messages, warnings and faults in the same list that this page doesn't cover: oL, RB, MT, EV, E.OPT, E.1, E.PE2, E.13, E.MB4–E.MB7, Er1–Er4, Err., HOLD, LOCD – see the manual for those.
Sources: Mitsubishi Electric, FR-E700 Instruction Manual (Basic), FR-E720-0.1KSC to 15KSC, FR-E740-0.4KSC to 15KSC, FR-E720S-0.1KSC to 2.2KSC, IB(NA)-0600458ENG-A (February 2011) – chapter 8, Troubleshooting: Reset method of protective function and List of fault displays; Mitsubishi Electric, FR-E700 Instruction Manual (Applied), CC-Link communication function models FR-E720-0.1KNC to 15KNC, FR-E740-0.4KNC to 15KNC, FR-E720S-0.1KNC to 2.2KNC, IB(NA)-0600402ENG-A (November 2011) – monitor description list (Pr. 52) and the retry function (Pr. 65, Pr. 67 to Pr. 69), read on October 17, 2026.
Meanings, causes and checks are summarized in our own words. The manuals are the reference: they have every code, the full corrective actions and the safety instructions. A newer revision of a manual may add codes, so check the current revision for your drive.
FR-E700 inverters in stock
Mitsubishi FR-E700 (FR-E720, FR-E740) part numbers on our shelves right now. Every item is photographed, so check the nameplate – catalog number and series – against the drive you're replacing.
- FR-E720-0.1KNCMitsubishi Electric FR-E720-0.1KNC 0.8-1.5A 3PH AC200-240V 50/60HZ 0.2-400HZ
- FR-E740-3Mitsubishi FR-E740-3. 7K 15. 1A 3PH AC380-480V 50/60Hz
- FR-E740-120-NAMitsubishi FR-E740-120-NA Inverter VFD AC Drive 7.5HP 16.8A 3PH 380-480V E700
- FR-E740-0Mitsubishi FR-E740-0. 75K 4.1A 3PH AC380-480V 50/60Hz
- FR-E740-095-NAMitsubishi FR-E740-095-NA E700 Inverter VFD Drive 9.5A 3PH 380-480V 50/60Hz
- FR-E740-120SC-NAMitsibishi Electric FR-E740-120SC-NA E700 16.8A 3PH AC380-480V50/60Hz Inverter
- FR-E740-3.7KMitsubishi FR-E740-3.7K Inverter VFD 3.7kW 380-480VAC 3PH 15.1A 50/60Hz Drive
- FR-E740-300SC-NAFR-E740-300SC-NA NEW MITSUBISHI FRE740300SCNA Inverter
Fault won't clear?
When the checks point to the drive itself – the manual's “replace the inverter” or “contact your sales representative” – send us the fault code and the catalog number from the nameplate. We check our shelves and our sourcing network and reply with a written quote. Purchase orders are welcome; payment is due before we ship.
Frequently asked questions
How do I reset a fault on a Mitsubishi FR-E700?
Fix the cause first and turn the start signal off – a reset with the start signal on restarts the motor at once. Then press STOP/RESET on the operation panel, turn on the RES signal for more than 0.1 s, or switch the power off and on again after the panel goes dark. A reset also clears the electronic thermal count and the retry count.
What does E.OC1 mean on a Mitsubishi FR-E700?
E.OC1 is the overcurrent trip during acceleration: output current went over the trip level while the motor sped up. Lengthen the acceleration time and check the output wiring and the motor for a short or a ground fault. E.OC2 is the same trip at constant speed and E.OC3 during deceleration or at a stop.
What is the difference between a fault, a warning and an alarm on an FR-E700?
A fault (E. and a code) shuts the inverter's output off and sends the fault signal until it is reset. Warnings and the FN fan alarm send no fault signal. OL and TH don't stop the output, but UV shuts it off until the supply recovers, PS follows a STOP/RESET press and SA is the safety stop. A warning that is ignored can turn into a fault.
Where can I see which faults an FR-E700 had?
In the operation panel's faults history mode: the past eight faults, each with the output frequency, current, voltage and energization time when it happened. Er.CL clears the history.
Can you supply a replacement FR-E700 inverter?
Send the model from the rating plate (for example FR-E740-...) and the fault code through our quote form. We check our shelves and our sourcing network and reply with a written quote.