Quick answer
An FR-D700 fault shows on the operation panel as E. and a short code – for example E.OC1: the inverter shuts off its output, sends its fault signal and stays stopped until it is reset. Warnings such as OL or TH and the FN fan alarm leave the output on, but the manual says an ignored warning leads to a fault. UV is listed as a warning yet stops the output until the supply voltage recovers, and SA means the safety stop is holding it off. Find the code below, fix the cause, make sure the start signal is off, then reset with the STOP/RESET key, the RES input or a power cycle.
Jump to a code:
Safety first: lock out and tag out the inverter and the machine before you open the inverter or touch the wiring, and follow Mitsubishi Electric's precautions in the manual. The smoothing capacitors stay charged after power is removed: the manual says to wait at least 10 minutes after the power is switched off and check that the operation panel display is off; then a qualified person verifies zero voltage with a properly rated meter, checking the meter on a known source before and after, and confirms that the voltage between main circuit terminals P/+ and N/– is no more than 30 V DC (safety instructions and pp. 50, 276) – a dark display alone doesn't mean it's safe. Never bypass the safety stop inputs (S1, S2) or any other safety circuit, and never switch off a fault or raise the retry count to keep a machine running – the retry function restarts the motor by itself. The STOP/RESET key may not stop the output with some settings, so the machine needs its own emergency stop. Only qualified personnel should work on inverters, and any measurement on energized equipment follows your site's live-work and arc-flash rules.
Reading and resetting an FR-D700 fault
- Note the code. The operation panel's fault history shows the last eight faults, each with the output frequency, current, voltage and energization time when it happened (manual p. 252). Er.CL clears the history.
- Look it up in the table below – each row gives the manual page – and fix the cause first: a fault whose cause is still there comes straight back.
- Reset it: turn the start signal (STF / STR) off first – the manual warns that resetting with the start signal still on starts the motor without warning – then press STOP/RESET, turn on the RES signal for more than 0.1 s, or switch the power off and back on once the panel has gone dark (p. 256). The inverter is ready about 1 s after the reset.
- Watch the restart. If the same code returns, go back through the checks before resetting again.
The table follows the FR-D700 Instruction Manual (Applied), revision H, for the FR-D720, FR-D740, FR-D720S and FR-D710W; the page numbers are the manual's printed page numbers. Codes marked “Off in the initial setting” only appear once their function has been turned on in the parameter named in the row.
Common FR-D700 fault codes
This list covers the codes technicians run into most often, not every code. The manual has the complete list and the full corrective actions.
| Code | What it means | Likely causes | First checks |
|---|---|---|---|
| E.OC1Overcurrent trip during accelerationFaultManual p. 261 | Output current reached about 200 % of the rated current while the motor was accelerating. |
|
|
| E.OC2Overcurrent trip during constant speedFaultManual p. 261 | Output current reached about 200 % of the rated current while running at a steady speed. |
|
|
| E.OC3Overcurrent trip during deceleration or stopFaultManual p. 262 | Output current reached about 200 % of the rated current while slowing down or stopped. |
|
|
| E.OV1Regenerative overvoltage trip during accelerationFaultManual p. 262 | Regenerated energy pushed the internal DC bus voltage over its limit while the motor was accelerating. |
|
|
| E.OV2Regenerative overvoltage trip during constant speedFaultManual p. 262 | Regenerated energy pushed the internal DC bus voltage over its limit while running at a steady speed. |
|
|
| E.OV3Regenerative overvoltage trip during deceleration or stopFaultManual p. 262 | Regenerated energy pushed the internal DC bus voltage over its limit while slowing down or stopped. |
|
|
| E.THTInverter overload trip (electronic thermal O/L relay function)FaultManual p. 263 | The electronic thermal protection for the inverter's output transistors tripped. |
|
|
| E.THMMotor overload trip (electronic thermal O/L relay function)FaultManual p. 263 | The inverter's electronic thermal protection for the motor tripped. |
|
|
| E.FINHeatsink overheatFaultManual p. 263 | The heatsink temperature sensor tripped the inverter. |
|
|
| E.ILFInput phase lossFaultOff in the initial settingManual p. 264, 149 | One of the three input phases was lost, or the phases are badly unbalanced (three-phase input models only). |
|
|
| E.OLTStall prevention stopFaultManual p. 264 | Stall prevention held the output at 1 Hz for 3 s because the load was too heavy. |
|
|
| E.BEBrake transistor alarm detectionFaultManual p. 264 | The inverter found a fault in its brake transistor circuit. |
|
|
| E.GFOutput side earth (ground) fault overcurrent at startFaultOff in the initial settingManual p. 264, 149 | A ground fault on the output side was found when the inverter started. |
|
|
| E.LFOutput phase lossFaultManual p. 264, 149 | One of the output phases (U, V, W) was lost while the inverter was running. |
|
|
| E.OHTExternal thermal relay operationFaultOff in the initial settingManual p. 265, 116 | A thermal relay or motor thermostat wired to the OH input opened. |
|
|
| E.PTCPTC thermistor operationFaultOff in the initial settingManual p. 265 | The motor's PTC thermistor on terminals 2 and 10 went over the Pr.561 resistance level. |
|
|
| E.PEParameter storage device fault (control circuit board)FaultManual p. 265 | The memory that stores the parameters (EEPROM) has a fault. |
|
|
| E.PUEPU disconnectionFaultManual p. 265, 161 | Communication with the parameter unit, or RS-485 on the PU connector, was lost. |
|
|
| E.RETRetry count excessFaultOff in the initial settingManual p. 265, 147 | The retry function could not restart the inverter within the set number of tries. |
|
|
| E.CPU / E.5CPU faultFaultManual p. 266 | A communication fault of the inverter's built-in CPU. |
|
|
| E.CDOOutput current detection value exceededFaultOff in the initial settingManual p. 266, 127 | Output current went over the Pr.150 detection level and Pr.167 is set to trip. |
|
|
| E.IOHInrush current limit circuit faultFaultManual p. 266 | The resistor in the inrush current limit circuit overheated. |
|
|
| E.AIEAnalog input faultFaultManual p. 266 | Terminal 4 got a signal while Pr.267 and the voltage / current input switch were set differently. |
|
|
| E.SAFSafety circuit faultFaultManual p. 266 | The safety circuit is malfunctioning, or the S1–SC or S2–SC safety stop line opened. |
|
|
| OLStall prevention (overcurrent)WarningManual p. 259 | Overcurrent stall prevention is working: the inverter holds back the frequency to limit the current. |
|
|
| UVUndervoltageWarningStops the outputManual p. 260 | Supply voltage dropped below about 115 V AC (200 V class) or 230 V AC (400 V class); the output stops until it recovers. |
|
|
| THElectronic thermal relay function pre-alarmWarningManual p. 260 | The electronic thermal value reached 85 % of the Pr.9 setting; at 100 % the inverter trips. |
|
|
| RBRegenerative brake pre-alarmWarningManual p. 260 | The regenerative brake duty reached 85 % of the Pr.70 setting; at 100 % an E.OV trip follows. |
|
|
| PSPU stopWarningManual p. 260, 161 | STOP/RESET on the operation panel was pressed while the inverter ran from another command source. |
|
|
| SASafety stopWarningOutput held offManual p. 261 | The safety stop function is active and holds the output off. |
|
|
| FNFan alarmAlarmManual p. 261 | The cooling fan stopped, or isn't running the way Pr.244 [Cooling fan operation selection] sets it. |
|
|
The name is the manual's own name for the code; the code is what the operation panel shows. The manual files UV and SA under warnings, but both hold the output off; the other warnings and the FN alarm don't trip the inverter. Other error messages and warnings in the same list that this page doesn't cover: oL, MT, HOLD, LOCD, Er1–Er4, Err., E--- – see the manual for those.
Source: Mitsubishi Electric, FR-D700 Instruction Manual (Applied), FR-D720-0.1K to 15K, FR-D740-0.4K to 15K, FR-D720S-0.1K to 2.2K, FR-D710W-0.1K to 0.75K, IB(NA)-0600366ENG-H (June 2018) – chapter 5, Troubleshooting (pages 255 to 266), with the parameter and maintenance pages named in each row – page numbers on this page are the manual's printed page numbers, read on October 17, 2026.
Meanings, causes and checks are summarized in our own words. The manual is the reference: it has every code, the full corrective actions and the safety instructions. A newer revision of the manual may add codes, so check the current revision for your drive.
FR-D700 inverters in stock
Mitsubishi FR-D700 (FR-D720, FR-D740, FR-D720S) part numbers on our shelves right now. Every item is photographed, so check the nameplate – catalog number and series – against the drive you're replacing.
- FR-D740-160-NAMitsubishi Electric FR-D740-160-NA 23.8A 3PH AC380-480V50/60Hz
- FR-D740-080-NAMitsubishi FR-D740-080-NA D700 VFD Inverter Drive 3 Phase 480V 3HP 2.2kW 8.0A
- FR-D740-120-NAMitsubishi FR-D740-120-NA 16.7A 3PH AC380-480V
- FR-D740-1Mitsubishi FR-D740-1. 5K AC380-480V 50/60Hz
- FR-D740-1.5KMitsubishi FR-D740-1.5K FREQROL D700 VFD Inverter 1.5kW 2HP 400V 3 Phase Drive
- FR-D720S-042-NAMitsubishi FR-D720S-042-NA Compact Inverter D700 VFD 0.75kW 1HP 200-240V 1PH
- FR-D740-050-NAMitsubishi FR-D740-050-NA D700
- FR-D740-5.5KMitsubishi Electric FR-D740-5.5K FR-D740-5.5K 50/60Hz
Fault won't clear?
When the checks point to the drive itself – the manual's “replace the inverter” or “contact your sales representative” – send us the fault code and the catalog number from the nameplate. We check our shelves and our sourcing network and reply with a written quote. Purchase orders are welcome; payment is due before we ship.
Frequently asked questions
How do I reset a fault on a Mitsubishi FR-D700?
Fix the cause first and turn the start signal off – resetting with the start signal still on starts the motor without warning. Then press STOP/RESET on the operation panel, turn on the RES signal for more than 0.1 s, or switch the power off and on again after the panel goes dark. A reset also clears the electronic thermal count and the retry count.
What does UV mean on a Mitsubishi FR-D700?
UV is undervoltage: the supply dropped below about 115 V AC on a 200 V class inverter (about 230 V AC on a 400 V class). The manual lists it as a warning, but the inverter stops its output until the voltage is back to normal. Read the DC bus on the panel with Pr.52 = 8, and leave checks of the live supply to a qualified electrician.
What is the difference between a fault, a warning and an alarm on an FR-D700?
A fault (E. and a code) shuts the inverter's output off and sends the fault signal until it is reset. Warnings (OL, TH, RB, PS ...) and the FN fan alarm leave the output on, though an ignored warning can turn into a fault; UV and SA are the exceptions that hold the output off.
Where can I see which faults an FR-D700 had?
In the operation panel's fault history: the last eight faults, each with the output frequency, current, voltage and energization time when it happened. Er.CL clears the history. We have separate pages for the FR-E700 and FR-E800.
Can you supply a replacement FR-D700 inverter?
Send the model from the rating plate (for example FR-D740-...) and the fault code through our quote form. We check our shelves and our sourcing network and reply with a written quote.